Wednesday, 23. May 2012 | 18:01 h

 
 

NYY

nyyPower cable for fixed installations

Technical data: NYY


CONSTRUCTION
1. Solid copper conductor, class 1, or stranded, class 2
2. PVC insulation
3. Filler layer
4. PVC sheath

TECHNICAL SPECIFICATION
Rated voltage: 0.6/1 kV
Test voltage: 4 kV
Perm.operating temperature: min. –40 °C max. +70 °C
Perm. temperature handling: min. +4 °C max. +40 °C
Min. perm. storage temperature: –40 °C
Use: For fixed outdoor installations in ground or in concrete.
Colour of sheath: black
Colour marking of cores according to: DIN 57 293/VDE 0293 – Idt. HD 308 S2:2001
Manufactured according to: DIN VDE 0276-603/1.2005
Standard packing: coils 100 m, drums, one-way reels
Note: Flame retardant according to ČSN EN 60332-1 (IEC 60332-1).

Product certificate:
VDE - NYY
Declaration of conformity: NYY