Wednesday, 23. May 2012 | 17:52 h

 
 

H05V2-U, H07V2-U

h05v2-uPVC insulated single core cables for indoor wiring

Technical data:
H05V2-U, H07V2-U


CONSTRUCTION
1. Stranded copper conductor, class 1
2. PVC insulation

TECHNICAL SPECIFICATION
Rated voltage:
300/500 V H05V2-U, 0,5; 0,75; 1
450/750 V H07V2-U, 1,5-10
Test voltage:
2 kV for H05V2-U, 0,5; 0,75; 1
2,5 kV for H07V2-U, 1,5-10
Perm. operating temperature: min. -15 °C max. +90 °C
Min. perm. temp.
- with installation and handling: +4 °C
- storage: -40 °C
Max. perm. storage temp.: +40 °C
Use:
In dry rooms, for fixed installation in conduits and under plaster, for appliance wiring and distribution stations.
Colour of sheath: black, white, grey, brown, blue, green/yellow, red; others acc. to the agreement
Manufactured according to: ČSN 34 7410-3 (HD 21.3 - S2)
Standard packing: coils 100 and 200 m in carton boxes, reels
Note: Flame retardation according to ČSN EN 60332-1 (IEC 60332-1).

Declaration of conformity:  H05V2U